Crossflow microsand filtration in cooling tower systems to control fouling in heat exchanger devices

Vaishali Ashok, Faezeh Absalan, Alain Silverwood, Étienne Robert, Dominique Claveau-Mallet and Émilie Bédard

Article (2024)

Open Acess document in PolyPublie and at official publisher
[img]
Preview
Open Access to the full text of this document
Published Version
Terms of Use: Creative Commons Attribution
Download (3MB)
[img]
Preview
Open Access to the full text of this document
Supplemental Material
Terms of Use: Creative Commons Attribution
Download (232kB)
Show abstract
Hide abstract

Abstract

In the context of global warming, there is a growing need for high-performance heat, ventilation and air conditioning systems. Fouling is a challenge, affecting heat exchanger operational and energetic performance. Side stream filtration can be used to improve water quality by reducing particle concentration in the system. The aim of this study was to assess a crossflow microsand filtration unit's efficacy in reducing fouling within an 81-plate heat exchanger, in an in-situ cooling tower circuit. A pilot heat exchanger without filtration was operated under similar conditions. After 3 years of continuous operation, visual inspection of the full-scale heat exchanger plates operating with filtration showed minimal accumulation. Pairs of facing plates (7) were scraped and rinsed to collect total solids accumulated on surfaces. Samples were resuspended and analyzed for solids and metal concentration measurements. Low average values of total volatile solids (45 μg/cm2) and total solids (93 μg/cm2) were indicative of a low biofilm formation. X-ray diffraction revealed the presence of calcite associated to water hardness. Low levels of iron and copper were detected despite slightly corrosive water. In contrast, the pilot heat exchanger exhibited higher deposit accumulation of total volatile solids (90 μg/cm2) and total solids (110 μg/cm2) after only 12 weeks of operation. These findings underscore the role of side stream filtration in reducing particle deposition and biofouling potential in full-scale cooling tower systems. Crossflow microsand filtration is a promising avenue to control fouling in building cooling tower systems, which could contribute in improving the building's energetic performance.

Uncontrolled Keywords

side stream filtration; building energy; HVAC; clogging

Subjects: 1000 Civil engineering > 1005 Hydraulic engineering
2100 Mechanical engineering > 2100 Mechanical engineering
Department: Department of Mechanical Engineering
Department of Civil, Geological and Mining Engineering
Funders: MITACS, Evoqua Water Technologies LLC
Grant number: IT27607
PolyPublie URL: https://publications.polymtl.ca/58888/
Journal Title: Journal of Building Engineering (vol. 95)
Publisher: Elsevier
DOI: 10.1016/j.jobe.2024.110167
Official URL: https://doi.org/10.1016/j.jobe.2024.110167
Date Deposited: 29 Jul 2024 13:39
Last Modified: 03 Sep 2024 02:55
Cite in APA 7: Ashok, V., Absalan, F., Silverwood, A., Robert, É., Claveau-Mallet, D., & Bédard, É. (2024). Crossflow microsand filtration in cooling tower systems to control fouling in heat exchanger devices. Journal of Building Engineering, 95, 110167 (11 pages). https://doi.org/10.1016/j.jobe.2024.110167