<  Back to the Polytechnique Montréal portal

Impact of recommissioning flushing on Legionella pneumophila in a large building during the COVID-19 pandemic

Marianne Grimard-Conea, Elise Deshommes, Evelyne Doré and Michèle Prévost

Article (2022)

Open Acess document in PolyPublie and at official publisher
[img]
Preview
Open Access to the full text of this document
Published Version
Terms of Use: Creative Commons Attribution
Download (2MB)
Show abstract
Hide abstract

Abstract

COVID-19 shutdowns drastically increased the frequency and duration of water stagnation events in building plumbing systems, urging local authorities to issue guidance for the safe reopening of buildings mostly by recommissioning flushing. The objectives of this study were to document the dynamic changes of bacterial indicators [adenosine triphosphate (ATP), total and intact cell counts (TCC, ICC)] and the prevalence of Legionella pneumophila (Lp) in 20–21 showerheads in a large building before (16-week building closure) and then shortly (24 h) and monthly (4-week of distal water stagnation) after targeted recommissioning flushing. Following the 16-week shutdown, the highest mean of ATP (10 pg ATP/mL), TCC (1.7 × 106 count/mL) and ICC (5.2 × 105 count/mL) were measured in first draw samples. This bacterial amplification was mostly attributable to detachment from biofilm present in the distal devices and immediate connecting piping. Culture-based (mean of 4 487 MPN/L) and quantitative polymerase chain reaction (qPCR; mean of 63 822 gu/L) concentrations of Lp were respectively measured in 81 and 90% of first draw samples. Individual flushing of showerheads for 5 min resulted in 1.2–278-fold decreases in ATP, whereas TCC and ICC were lowered by 1.1- and 0.7-log on average. A one-log reduction in culture-based and qPCR Lp was only achieved in 63 and 29% of paired water samples, resulting in less than one-log reduction in mean risk values per exposure, thus demonstrating the limited effects of fixture-flushing for risk reduction. Clear short-term (24 h) benefits of device recommissioning flushing included lowered values of all bacterial indicators and Lp levels systematically under the common alert threshold of 1 000 MPN/L in first draws. However, after a period of 1 month without water use, these benefits were mostly lost with considerable rebounds of concentrations to similar levels than those measured following the 16-week building closure. Results highlight the temporary benefits of device recommissioning flushing for the control of Lp in shower systems, especially in buildings colonized by Legionella.

Uncontrolled Keywords

legionella; flushing; recommissioning; stagnation; building plumbing; COVID-19

Subjects: 1000 Civil engineering > 1001 Construction engineering and management
1000 Civil engineering > 1007 Water resources and supply
Department: Department of Civil, Geological and Mining Engineering
Research Center: Other
PolyPublie URL: https://publications.polymtl.ca/51919/
Journal Title: Frontiers in Water (vol. 4)
Publisher: Frontiers media sa
DOI: 10.3389/frwa.2022.959689
Official URL: https://doi.org/10.3389/frwa.2022.959689
Date Deposited: 18 Apr 2023 14:58
Last Modified: 30 Sep 2024 17:09
Cite in APA 7: Grimard-Conea, M., Deshommes, E., Doré, E., & Prévost, M. (2022). Impact of recommissioning flushing on Legionella pneumophila in a large building during the COVID-19 pandemic. Frontiers in Water, 4, 959689 (18 pages). https://doi.org/10.3389/frwa.2022.959689