A model-based continuous commissioning method for an efficient integration of ground source heat pumps in the building ecosystem

Giulio Tonellato, Michaël Kummert, José A. Candanedo, Gabrielle Beaudry and Philippe Pasquier

Article (2025)

Open Acess document in PolyPublie and at official publisher
[img]
Preview
Open Access to the full text of this document
Published Version
Terms of Use: Creative Commons Attribution
Download (7MB)
Show abstract
Hide abstract

Abstract

This paper introduces a model-based continuous commissioning (MBCCx) methodology specifically designed for the identification of control-related performance gaps within heating, ventilation and air conditioning (HVAC) systems equipped with ground-source heat pumps (GSHPs). While conventional continuous commissioning (CCx) is effective in detecting energy performance gaps, MBCCx goes further by using a system model as a reference to pinpoint operational inefficiencies and control faults arising from subsystem integration. The core of the proposed methodology lies in a calibrated physics-based model that represents the system performance as intended during the design phase. A key advantage is its applicability early in a building’s operational phase, when data is limited, unlike data-driven methods that rely on extensive historical datasets. This enables the identification of energy-saving opportunities before the system reaches a stable operational state. To address the limitations of prior studies that often focus solely on individual GSHP component performance, this work pioneers the application of MBCCx to whole buildings equipped with GSHPs. The proposed approach employs a detailed 3D building model and component-level HVAC modeling to predict parameters such as room temperatures, heat pump power, and ground heat exchanger temperatures under normal conditions. Significant deviations between monitored values and model predictions serve as indicators of underperforming components or control sequence anomalies. The anomaly detection accuracy is then improved by merging HVAC system and GSHP performance indicators. The methodology is demonstrated through a case study of a recently retrofitted elementary school in Québec, Canada, equipped with five standing column wells as ground heat exchangers.

Uncontrolled Keywords

Department: Department of Mechanical Engineering
Department of Civil, Geological and Mining Engineering
Funders: NSERC / CRSNG, Geothermal Research Chair on the Integration of SCWs in Institutional Buildings, Hydro-Québec, Quebec - Ministry of higher education, Centre de services scolaire des Mille-îles (CSSMI), Centre de services scolaire de Montréal (CSSDM), Centres intégrés de santé et de services sociaux (CISSS), Versa Profiles, Marmott Energies, CanmetEnergy
Grant number: ALLRP 544477-19
PolyPublie URL: https://publications.polymtl.ca/62964/
Journal Title: Energy and Buildings (vol. 333)
Publisher: Elsevier
DOI: 10.1016/j.enbuild.2025.115492
Official URL: https://doi.org/10.1016/j.enbuild.2025.115492
Date Deposited: 24 Feb 2025 10:27
Last Modified: 10 Jan 2026 15:49
Cite in APA 7: Tonellato, G., Kummert, M., Candanedo, J. A., Beaudry, G., & Pasquier, P. (2025). A model-based continuous commissioning method for an efficient integration of ground source heat pumps in the building ecosystem. Energy and Buildings, 333, 115492 (15 pages). https://doi.org/10.1016/j.enbuild.2025.115492

Statistics

Total downloads

Downloads per month in the last year

Origin of downloads

Dimensions

Repository Staff Only

View Item View Item